Generate a site-specific acoustic setback report and radial contour drawing for Rehlko (formerly Kohler) 14RCA & 20RCA installations.
Instant self-serve download + 30-Day Magic Edit Link (change address or numbers anytime free).
| Ln | Description & Prescriptive Formula | Code Ref | Input | Calculated |
|---|
Below is a complete step-by-step mathematical schedule generated from standard nameplate ratings so municipal plan examiners, homeowners, and contractors can verify every code formula:
| Line | Step Description & Formula | Code Reference | Rating | Calculated |
|---|---|---|---|---|
| 1 | Published Sound Pressure Level (Lp) @ 23 ft Reference — Rehlko (Kohler) 20RCA 20kW Standby Generator | Mfr Spec (Lp) | 64.0 dB(A) | 64.0 dB |
| 2 | Inverse-Square Distance Attenuation to 32.0 ft Setback: -20·log10(32.0 / 23.0) | ISO 9613-2 / Inv.Sq. | 32.0 ft | -2.9 dB |
| 3 | Reflective Surface Directivity Adjustment: Adjacent Exterior Wall Reflection (Q=2) | Directivity Q Factor | Q=2 | +3.0 dB |
| 4 | Line-of-Sight Acoustic Barrier / Ventilated Sound Enclosure Insertion Loss | Maekawa / STC Barrier | -9 dBA Rated | -9.0 dB |
| 5 | Predicted Sound Pressure Level at Nearest Property Line (Max Limit: 55.0 dBA) | Boundary Compliance | Limit 55.0 dBA | 55.1 dB(A) |
The 20RCA air-cooled standby generator is rated at approximately 64 dB(A) under normal load and ~52 dB(A) during weekly exercise at 23 feet (7 meters).